This guide provides essential information for the nVent CADDY Push-In Conduit to Conduit Clamp. This device is designed to act as a spacer between conduits of the same or different sizes. Installation requires no tools. Please note that the top conduit is intended for support only and not as a raceway.

Product Overview

The clamp is constructed from Spring Steel with an nVent CADDY Armour finish. It is available in several models to accommodate different conduit sizes (EMT and Rigid).

nVent CADDY Push-In Conduit to Conduit Clamp
nVent CADDY Push-In Conduit to Conduit Clamp
Installation diagram showing conduit stacking
Installation diagram showing conduit stacking

Specifications

All models have an Ultimate Static Load capacity of 25 lb. Please refer to the table below for specific conduit compatibility:

  • 12P12P: 3/4" EMT / 1/2" Rigid
  • 12P16P: 3/4" EMT / 1/2" Rigid to 1" EMT / 3/4" Rigid
  • 8P12P: 1/2" EMT / 1/2" Rigid to 3/4" EMT
  • 8P16P: 1/2" EMT / 3/4" Rigid to 1" EMT
  • 8P8P: 1/2" EMT
  • 16P16P: 1" EMT / 3/4" Rigid

Safety Warnings

Improper installation, misuse, or failure to follow nVent instructions may cause product malfunction, property damage, serious bodily injury, or death. Always install as indicated in the product instruction sheets.

Practical help

Common problems

Exceeding load capacity

Ensure the total load does not exceed the Ultimate Static Load of 25 lb.

Incorrect conduit size

Verify the conduit diameter matches the specifications for your specific catalog number.

Before use

  • Verify the catalog number matches your conduit size requirements.
  • Ensure the installation surface is suitable for the load.
  • Check that the conduit is not being used as a raceway if it is the top conduit.

Specs in practice

Ultimate Static Load
The maximum weight the clamp can support, which is 25 lb for all models.
nVent CADDY Armour
The protective finish applied to the spring steel clamp.

Images and diagrams

  • The diagram illustrates the vertical stacking of two conduits using the clamp, showing the orientation of the clamp relative to the conduits.

Model compatibility

  • Compatible with both EMT and Rigid conduit types depending on the specific model.
  • Top conduit is for support only.