This guide provides essential installation instructions for the Danfoss ELIMINATOR Type DCL hermetic filter drier with an access port. It covers refrigerant compatibility, brazing requirements, and torque settings for the access port valve.

Application and Compatibility

The filter drier is compatible with a wide range of refrigerants, including R22, R23, R32, R1234yf, R1234ze, R134a, R404A, R407A, R407C, R407F, R410A, R444B, R448A, R449A, R450A, R452A, R507, and R513A. For other refrigerants, please contact Danfoss. The operating media temperature range is -40 °C to 70 °C (-40 °F to 160 °F).

Installation

Follow these steps for proper installation:

Brazing and temperature requirements for installation
Brazing and temperature requirements for installation
  • Brazing: Use a minimum of 5% silver (Ag) content for brazing.
  • Valve Protection: You must remove the Schrader valve before brazing to prevent damage.
  • Temperature Control: Ensure the filter body temperature does not exceed 70 °C (160 °F) during the process.
  • Surface Protection: If any paint is burnt off during brazing, clean the area and apply anti-corrosion paint or heat shrink to prevent rust.
  • Access Port: After installation, ensure the access port is tightened to 0.5 Nm (5 in.-lbs) and the valve core to 1.5 Nm (13 in.-lbs).
  • System Marking: After charging the system, clearly mark it with the type of refrigerant and oil used.

Converting from capillary tube

If converting from a 2.8 mm capillary tube outlet to a 1/4 inch connection, use the designated cutting line indicated on the filter drier outlet tube.

Manufacturer information

Danfoss A/S

Brand profile

Practical help

Common problems

Burnt paint on the filter body after brazing

Clean the affected area and apply anti-corrosion paint or heat shrink to protect the metal.

Damage to the Schrader valve during installation

Always remove the Schrader valve before performing any brazing operations.

Before use

  • Verify the refrigerant type is on the approved list.
  • Ensure brazing material has at least 5% silver content.
  • Check that the Schrader valve has been removed before heating.
  • Confirm the system is marked with refrigerant and oil type after charging.

Specs in practice

Media Temperature
Operating range of -40 °C to 70 °C.
Brazing Torque
Access port valve core must be tightened to 1.5 Nm (13 in.-lbs).

Images and diagrams

  • The diagram illustrates the brazing process, highlighting the need to keep the filter body below 70 °C.
  • The conversion diagram shows the specific cutting line for transitioning from a 2.8 mm capillary tube to a 1/4 inch connection.

Model compatibility

  • Compatible with R22, R23, R32, R1234yf, R1234ze, R134a, R404A, R407A, R407C, R407F, R410A, R444B, R448A, R449A, R450A, R452A, R507, and R513A.