Danfoss 020R5421 Type OFC Check and Stop Valve Installation Guide
Installation and maintenance guide for Danfoss 020R5421 Type OFC Check and Stop Valve. Includes orientation requirements, spring color coding, torque specifications, and refrigerant compatibility.
Table of contents
Quick guide from the manual
The Danfoss Type OFC Check and Stop Valve is designed for oil-free environments, specifically for use with Danfoss Turbocor compressors. The valve must be installed in a vertical down orientation as delivered. If other orientations are required, the internal check valve spring must be replaced with the color-coded spring corresponding to the specific angle.
Technical Specifications
- Refrigerants: UL listed for R134a, R513A, R515B; CE approved for fluid group 2, including R1234ze(E).
- Media Temperature: Min 0°C / 32°F; Max 90°C / 194°F (short term up to 100°C / 212°F).
- Max Working Pressure: 23 bar / 334 psig.
- Environment: Oil-free.
Installation
Install the valve directly on the Danfoss Turbocor compressor. Protect the valve from impact during installation. All fasteners and bolts must be stainless steel with a minimum class of A2-70.
- Staging Port: Bolt size M10x1.5, Torque 38 Nm ± 4 Nm.
- Outlet Flange Fasteners: Torque 110 Nm.
- Brazing: Place outer flange on evenly cut copper pipe. Ensure the flange is not mounted on the main housing during brazing. Use minimum 5% Ag.
Orientation and Spring Configuration
The valve is delivered with a blue spring for vertical down installation. If the orientation is changed, the spring must be replaced:
- Vertical down: Blue spring (as delivered).
- 45° down: Yellow spring.
- Horizontal: Red spring.
- 45° up / Vertical up: Not allowed.
Maintenance: Changing the Check Valve Spring
- Remove the check valve insert from the main housing.
- Remove the check valve head.
- Remove the spring and replace it with the correct color based on the intended orientation.
- Replace the check valve head and insert.
- Install the outlet flange, O-ring, and fasteners.
Note: Always apply provided lubrication to the O-ring. Use silicone lubricant spray at the O-ring if needed. For check and stop valves, always replace the lock ring and cap after opening/closing the ball valve.
Manufacturer information
Danfoss A/S
Practical help
Common problems
Replace the internal check valve spring with the color-coded spring matching the new orientation (Yellow for 45° down, Red for horizontal).
Ensure the flange is not mounted on the main housing during the brazing process.
Apply provided lubrication to the O-ring; use silicone lubricant spray if necessary.
Before use
- Verify refrigerant compatibility (R134a, R513A, R515B, R1234ze(E)).
- Ensure the system is oil-free.
- Check that media temperature is within 0°C to 90°C.
- Use stainless steel fasteners (min class A2-70).
- Verify torque settings: 38 Nm for staging port, 110 Nm for outlet flange.
Specs in practice
- Max Working Pressure
- 23 bar / 334 psig.
- Staging Port Torque
- 38 Nm ± 4 Nm.
- Outlet Flange Torque
- 110 Nm.
- Media Temperature
- 0°C to 90°C (short term 100°C).
Model compatibility
- Designed specifically for Danfoss Turbocor compressors.
- Not compatible with oil-based systems.