Installation Guide for Danfoss 023R9615 Hermetic Filter Drier
Quick installation guide for the Danfoss 023R9615 Hermetic Filter Drier. Includes assembly steps, torque specifications, and safety requirements for proper installation.
Table of contents
Manual images
Click an image to enlargeQuick Installation Guide
This document provides essential installation instructions for the Danfoss modulinQ® Hermetic filter drier (Type DMC / DCC). Proper installation is critical for system integrity and safety. Ensure all components are compatible and that you have the necessary tools before beginning.
Technical Specifications
- Refrigerant: R290 (check official Danfoss website for complete list of approved refrigerants).
- Media Temperature: -40 °C to +85 °C.
- Max Working Pressure (MWP/PS): 49 bar.
- Max Tilt: +/- 10° from vertical.
- Support: Obligatory clamping is required.
Installation Procedure
Follow these steps to install the filter drier correctly:



- Preparation: Remove any dirt or debris from the connection areas. Compressed air may be used optionally.
- Pre-assembly: Apply oil (e.g., Reniso Triton SE 55) to the metal seal. Insert the metal seal into the bottom part. Ensure the O-rings are correctly positioned.
- Tightening: Connect the top and bottom parts. Tighten to a torque of 60 +/- 12 Nm. Use a counter-wrench to hold the assembly steady during tightening.
Safety and Maintenance
- Seals: Always discard used metal seals and O-rings. Never reuse them. Always use dedicated, new metal seals and O-rings for every installation.
- System Integration: The modulinQ® Hermetic receiver filter drier must be connected to a modulinQ® Expansion module.
Manufacturer information
Danfoss A/S
Practical help
Common problems
Ensure that new metal seals and O-rings are used. Never reuse old seals.
Ensure the connection is tightened to the specified torque of 60 +/- 12 Nm.
The unit must be installed within +/- 10° of the vertical position.
Before use
- Verify the refrigerant is compatible (R290).
- Ensure the modulinQ® Expansion module is available for connection.
- Clean all mating surfaces of dirt and debris.
- Obtain new, dedicated metal seals and O-rings.
- Prepare oil (e.g., Reniso Triton SE 55) for the seal.
Specs in practice
- MWP/PS: 49 bar
- Maximum Working Pressure allowed for the unit.
- Torque: 60 +/- 12 Nm
- Required tightening force for the connection to ensure a proper seal.
Images and diagrams
- Step 1 shows the cleaning of the connection area.
- Step 2 illustrates the placement of the metal seal and O-rings.
- Step 3 demonstrates the tightening process using a counter-wrench.
Model compatibility
- Must be connected to a modulinQ® Expansion module.
- Compatible with R290 refrigerant.