findmanualpdf.com

User Manual for EnviroVent Eco dMEV+ 17V Extract Fan

Quick guide for the EnviroVent Eco dMEV+ 17V extract fan. Includes installation, wiring diagrams, dip switch settings for airflow and humidity, and maintenance instructions.

Quick answers from the manual

Quick answer

  • The Eco dMEV+ 17V is a continuous extract fan. Installation requires a 105mm hole. Settings for airflow, timer, and humidity are configured via dip switches on the PCB. p. 10, 11, 12

Key actions

  • Clean the filter every two months. p. 13
  • Configure settings using dip switches. p. 11, 12

Problems and fixes

Fan never runs on boost

Check humidity sensor setting or room humidity level.

p. 13

Maintenance and reset

  • Clean filter every two months. p. 13

Technical specifications

Parameter Value Meaning Pages
Voltage 230Vac 50/60Hz Power supply requirements. p. 6, 11
Fuse 125mA max Time-delay fuse requirement. p. 6

Where to find it in the PDF

  • Installation p. 10, 11
  • Wiring Diagrams p. 6, 7, 8, 9
Table of contents

Manual images

Click an image to enlarge

Quick guide from the manual

The EnviroVent Eco dMEV+ 17V is a decentralised mechanical extract ventilation fan designed for continuous operation. It is suitable for wall or ceiling mounting. Before installation, ensure the mains supply is disconnected. The unit requires a 105mm hole in the wall or ceiling. If using ducting, use a standard 100mm duct.

Installation

The unit can be mounted on the wall or ceiling using the provided screws and raw plugs. Ensure there are no obstructions to the airflow and that the impeller turns freely. The unit is Class II (double insulated) and does not require an earth connection.

  • Make a 105mm hole in the wall or ceiling.
  • If installing with ducting, use a 100mm standard duct.
  • Introduce the mains cable through the cable entry (5).
  • Fix the unit to the wall or ceiling.
  • Connect the electrical wiring according to the applicable diagram.
  • Mount the protection cover and front grille.

Electrical Connection

The electrical installation must include a double pole switch with a contact clearance of at least 3mm. The unit is designed for a single-phase supply with voltage and frequency as indicated on the rating plate.

Wiring diagram for Eco dMEV+ 17V
Wiring diagram for Eco dMEV+ 17V

Operation and Settings

The fan operates continuously at low speed and constant volume. Settings are adjusted via dip switches located on the electronic circuit board (Fig. 1b). The fan may also operate at high speed (boost) activated by an external switch, light switch, or humidity sensor (depending on the model).

Dip switch location
Dip switch location

Dip Switch Settings

  • Airflow: Configured using SW2, SW3, and SW4.
  • Timer: Configured using SW6 and SW7 (1, 5, 15, or 30 minutes).
  • Humidity Sensor: Configured using SW8 and SW9 (60%, 70%, 80%, or 90% RH).

Factory Settings: Airflow 8l/s, Timer 1 minute, Humidity 60% RH.

Maintenance

Performance depends on cleaning frequency. We recommend cleaning the filter at least every two months. The fan must always be operated with the filter fitted; using it without the filter invalidates the warranty. Clean the external surface with a cloth lightly impregnated with a soft detergent.

Filter cleaning procedure
Filter cleaning procedure

Troubleshooting

If the fan never runs on boost, check if the humidity sensor is set to maximum or if the room humidity is below 60% RH. If the fan always runs on boost, check if the humidity sensor is set to minimum or if the room humidity is above 90% RH.

Practical help

Common problems

Fan never runs on boost

Check if the humidity sensor is set to maximum or if the room humidity is below 60% RH.

Fan always runs on boost

Check if the humidity sensor is set to minimum or if the room humidity is above 90% RH.

Before use

  • Ensure mains supply is disconnected before installation.
  • Verify the model and voltage/frequency on the rating label.
  • Ensure the impeller turns freely.
  • Use a double pole switch with at least 3mm contact clearance.
  • Ensure the filter is fitted before operation.

Specs in practice

Constant Volume
Fan operates continuously at low speed.
Humidity Sensor
Adjustable threshold from 60% to 90% RH.

Images and diagrams

  • Fig 1a: Filter cleaning procedure.
  • Fig 1b: Dip switch locations and identification.
  • Fig 3-6: Wiring diagrams for different connection scenarios.

Model compatibility

  • Suitable for wall or ceiling mounting.
  • Requires 105mm hole.
  • If using ducting, use 100mm standard duct.

Manual page author

Emily Carter

User documentation editor

Prepares concise manual descriptions and highlights the most useful setup, operation, and maintenance information for readers.