User Guide for Shelly Plus 0-10V Dimmer

Quick start guide for the Shelly Plus 0-10V Dimmer. Learn about installation, wiring, safety precautions, and initial setup for this smart dimming controller.

Table of contents

Quick guide from the manual

The Shelly Plus 0-10V Dimmer is a smart controller designed for 0-10V dimmable LED drivers. It allows for remote control of lighting circuits via Wi-Fi or Bluetooth using the Shelly Smart Control app or a web browser. Installation must be performed by a qualified electrician. Ensure the power is disconnected before starting any wiring work.

Installation

The device is designed to be installed in standard electrical wall boxes, behind power sockets or light switches. It requires a 110-240 VAC power supply.

Wiring

  • L (Live): Connect to the Live wire (110-240 VAC).
  • N (Neutral): Connect to the Neutral wire.
  • S1/S2: Connect to external switches or buttons.
  • Dim+/Dim-: Connect to the 0-10V input of the LED driver.

The device supports single or dual button modes and single switch mode. In single input mode, S2 is always detached.

Initial Inclusion

To set up the device, connect it to your Wi-Fi network. You can use the Shelly Smart Control mobile application or access the embedded Web Interface by navigating to http://192.168.33.1 when connected to the device's access point.

Safety

  • Danger of electrocution: Installation must be performed by a qualified electrician.
  • Circuit Protection: The device must be protected by a circuit breaker (characteristic B or C, max 2A, min 6kA interrupting rating).
  • Load Limit: Do not exceed the maximum load of 2A.
  • Compatibility: Do not use buttons or switches with built-in LED or glow-lamp.
  • Handling: Do not open the device or attempt to repair it yourself.

Practical help

Common problems

Device not connecting to Wi-Fi

Ensure the device is in Access Point mode or check your router settings. Use the Shelly Smart Control app to configure network settings.

Dimming not working

Verify the 0-10V polarity (Dim+ and Dim-) and ensure the LED driver is compatible with 0-10V sinking control.

Switch not responding

Check wiring to S1/S2 terminals. Ensure the switch does not have a built-in LED or glow-lamp, as these can interfere with operation.

Before use

  • Ensure power is turned off at the breaker before installation.
  • Verify the LED driver supports 0-10V sinking control.
  • Check that the load does not exceed 2A.
  • Use solid single-core wires or stranded wires with ferrules.
  • Confirm the circuit is protected by a breaker (max 2A).

Specs in practice

0-10V Control Type
Sinking (requires a compatible 0-10V LED driver).
Max Control Current
35 mA (maximum current the dimmer can sink).
Power Supply
110-240 VAC, 50/60Hz.
Operating Temperature
-20 °C to 40 °C.

Model compatibility

  • Not intended to directly control LED lights (requires a 0-10V LED driver).
  • Do not use buttons or switches with built-in LED or glow-lamp.