Corning 008T88-31180-29 MIC Tight-Buffered Cable Specification
Quick guide for the Corning 008T88-31180-29 MIC Tight-Buffered Cable. Includes technical specifications, environmental conditions, mechanical limits, and installation standards.
Table of contents
Quick guide from the manual
This document provides technical specifications for the Corning MIC Tight-Buffered Cable (Part Number 008T88-31180-29). This cable is designed for indoor use in plenum, riser, and general-purpose environments. It features an all-dielectric construction, which eliminates the need for grounding or bonding during installation.
Product Description
The cable utilizes 900 µm buffered fibers to facilitate easy and consistent stripping and termination. The fibers are protected by dielectric strength members and a flame-retardant outer jacket. It is ideal for routing inside buildings, within plenum areas, and riser shafts to telecommunications rooms and workstations.

Mechanical Specifications
Adhering to these mechanical limits is essential for maintaining signal integrity:
- Max. Tensile Strength (Long-Term, ≤12F): 132 N (29.67 lbf)
- Max. Tensile Strength (Short-Term, ≤12F): 440 N (98.92 lbf)
- Min. Bend Radius (Installation): 89 mm (3.5 in)
- Min. Bend Radius (Operation): 59 mm (2.32 in)
- Nominal Outer Diameter: 5.9 mm (0.23 in)
Environmental Conditions
Ensure the installation and operating environments remain within the following temperature ranges:
- Installation Temperature: 0 °C to 60 °C (32 °F to 140 °F)
- Operation Temperature: 0 °C to 70 °C (32 °F to 158 °F)
- Storage Temperature: -40 °C to 70 °C (-40 °F to 158 °F)
Standards and Compliance
The cable meets the application requirements of the National Electrical Code (NEC) Article 770 and is OFNP and FT-6 listed. It complies with the following standards:
- Approvals: NEC OFNP, NFPA 262, CSA FT-6, ICEA S-83-596
- Flame Test Method: NFPA 262 and CSA FT-6 (for plenum, riser, and general building applications)
Manufacturer information
Corning Optical Communications
Practical help
Common problems
Ensure the cable is not bent beyond the minimum bend radius (89 mm during installation, 59 mm during operation).
Do not install or operate the cable outside the specified temperature ranges (0°C to 60°C for installation; 0°C to 70°C for operation).
Before use
- Verify the part number 008T88-31180-29 matches your project requirements.
- Ensure the installation environment is indoor (plenum, riser, or general purpose).
- Confirm the cable path allows for the minimum installation bend radius of 89 mm.
- Check that the environment temperature is within the 0°C to 60°C range during installation.
Specs in practice
- Flame Rating
- Plenum (OFNP) rated, suitable for use in air-handling spaces.
- All-dielectric construction
- The cable contains no metal, so no grounding or bonding is required.
Images and diagrams
- The cross-section diagram illustrates the internal structure, including the flame-retardant outer jacket, dielectric strength members, and the 8 tight-buffered fibers.
Model compatibility
- Meets NEC Article 770 requirements.
- Compliant with NFPA 262 and CSA FT-6 flame test methods.
- Suitable for intrabuilding backbone and horizontal installations.