findmanualpdf.com

RAB HIDFA-115S-V-EX39-8CCT-BYP-3SP LED Lamp Installation Manual

Quick installation guide for the RAB HIDFA-115S-V-EX39-8CCT-BYP-3SP LED lamp. Includes wiring instructions, power and CCT selection settings, and safety warnings for high bay retrofitting.

Table of contents

Manual images

Click an image to enlarge

Quick Guide

The RAB HIDFA-115S-V-EX39-8CCT-BYP-3SP is a high-bay LED retrofit lamp. Crucial: This lamp requires the existing ballast, capacitor, and ignitor to be bypassed or removed before installation. It features selectable power (60W, 80W, 115W) and selectable color temperature (3000K, 4000K, 5000K) via switches on the lamp body.

Safety Warnings

  • High Voltage: Ensure the main power is turned off before installation.
  • Ballast Bypass: Do not operate on existing ballasts. The ballast, capacitor, and ignitor must be removed or bypassed.
  • Dimming: Do not use with standard dimmers. Use only specified controls.
  • Environment: For use in enclosed fixtures. Not intended for emergency exits.
  • Safety Cable: Must be used for base-up burning positions to prevent the lamp from falling due to old sockets.

Installation Instructions

Wiring diagram showing the bypass of ballast, capacitor, and ignitor.
Wiring diagram showing the bypass of ballast, capacitor, and ignitor.
  1. Power Off: Turn off the main power supply before starting.
  2. Bypass Ballast: Remove or bypass the existing ballast, capacitor, and ignitor.
  3. Wiring: Connect the alternating current wires directly to the socket. Reattach or replace the ground lead if necessary.
  4. Settings: Select the desired wattage and color temperature using the switches on the lamp before installing.
  5. Mounting: Screw the LED lamp into the corresponding socket.
  6. Safety Cable: Securely fasten the safety cable to the main body structure.

Power and CCT Selection

The lamp allows for customization of output:

Power and CCT selection switches.
Power and CCT selection switches.
  • Power Selectable: Choose between 60W, 80W, or 115W using the Power Selectable Switch.
  • Color Selectable: Choose between 3000K, 4000K, or 5000K using the Color Selectable Switch.

Maintenance

If the safety cable is damaged, it must be replaced. Use a cable that is 1.0mm in size and heat-insulated. Ensure the lamp is installed in the base-up position for optimal performance and safety.

Safety cable attachment.
Safety cable attachment.

Practical help

Common problems

Lamp does not turn on

Verify that the ballast, capacitor, and ignitor have been completely bypassed or removed from the circuit.

Lamp falls from socket

Ensure the safety cable is securely attached to the main body structure, especially in base-up burning positions.

Flickering or dimming issues

Ensure no standard incandescent dimmer is connected to the circuit.

Before use

  • Turn off the main power supply.
  • Remove or bypass the existing ballast, capacitor, and ignitor.
  • Verify the fixture is an enclosed type.
  • Select the desired wattage (60W/80W/115W) using the switch.
  • Select the desired color temperature (3000K/4000K/5000K) using the switch.
  • Ensure the safety cable is ready for attachment.

Specs in practice

Power Selectable
Allows adjustment of power consumption between 60W, 80W, and 115W.
CCT Selectable
Allows adjustment of color temperature between 3000K (warm), 4000K (neutral), and 5000K (cool).
Burning Position
The lamp is designed for base-up installation.

Images and diagrams

  • Wiring diagram shows the removal of the ballast, capacitor, and ignitor, connecting AC power directly to the lampholder.
  • Safety cable diagram illustrates the attachment point on the lamp base.

Model compatibility

  • Not compatible with standard dimmers.
  • Not for use in emergency exit fixtures.
  • Must be used in enclosed fixtures.

Manual page author

David Miller

Documentation analyst