Sanela SLU 25K Wall-Mounted Thermostatic Mixer Instruction Manual

Quick guide for the Sanela SLU 25K wall-mounted thermostatic mixer. Includes installation steps, electrical connection requirements, sensor settings, and annual maintenance procedures.

Table of contents

Quick guide from the manual

This document provides installation and operational instructions for the Sanela SLU 25K wall-mounted thermostatic mixer. The unit requires a constant 24V DC power supply for proper operation. Key maintenance includes an annual check of the electromagnetic valve filter and tightening of electrical connections.

Installation

The mixer is designed for wall mounting with a water inlet spacing of 100mm. Ensure the water pressure is between 0.1 and 0.6 MPa. The sieve dimension in the valve must be ≤ 90 µm. Connect the unit to a 24V DC power source. Important: Do not connect the power supply behind a light switch; the unit must remain under constant voltage to function correctly.

Operation and Settings

The mixer features an infrared sensor for automatic water flow. The sensor range is adjustable (factory setting 12 cm). The automatic stop function is set to 310 seconds by default. Advanced settings, such as hygienic flush intervals and durations, can be adjusted using the optional SLD 03 remote control.

Maintenance

To ensure long-term reliability, perform the following maintenance at least once a year:

  • Inspect and clean the electromagnetic valve filter to prevent clogging from water impurities.
  • Check and tighten all screw connections.
  • Inspect the contact surfaces of electrical connectors.

Manufacturer information

SANELA spol. s r. o.

Brand profile

Practical help

Common problems

Water flow stops automatically after 5 minutes

This is a standard safety feature. If the sensor is continuously triggered, the unit will stop flow after 5 minutes.

Unit does not function or behaves erratically

Ensure the unit is connected to a constant 24V DC power supply and not wired through a light switch.

Reduced water flow or valve blockage

The electromagnetic valve filter may be clogged with impurities. Clean the filter at least once a year.

Before use

  • Verify water pressure is between 0.1 and 0.6 MPa.
  • Ensure the power supply is 24V DC.
  • Confirm the power supply is not connected to a switched circuit.
  • Check that the water inlet spacing is 100mm.
  • Ensure the sieve dimension is ≤ 90 µm.

Model compatibility

  • Compatible with SLD 03 remote control for parameter adjustments.
  • Compatible with SLZ series external power supplies (24V DC).