User Manual for BEA Rim-Exit Electric Strike
Quick guide for the BEA Rim-Exit Electric Strike. Includes installation steps, wiring diagrams, technical specifications, and fail-safe/fail-secure configuration instructions.
Table of contents
Important Information
This document provides installation and configuration instructions for the BEA Rim-Exit Electric Strike. It is intended for use with UL-listed, rim-type fire exit hardware. Ensure all wiring complies with NFPA70 standards. The device is field-selectable for fail-safe or fail-secure operation.
Technical Specifications
- Operating voltage: 12 or 24 VDC
- Current draw: 540mA (12 VDC) / 270mA (24 VDC)
- Operating temperature: 14 to 120 °F (-10 to 49 °C)
- Humidity: 0 to 85% non-condensing
- Static strength: 1500 lbs (680kg)
- Lock mode: Field selectable fail-safe or fail-secure
- Material: Brushed stainless steel (US32D)
Safety Requirements
- Shut off all power to the electrical enclosure before wiring.
- Maintain a clean and safe environment.
- Be aware of pedestrian traffic; stop traffic when performing tests.
- Use ESD protection when handling circuit boards.
- Ensure moving door parts do not catch any wires.
- Do not attempt internal repairs; unauthorized disassembly voids the warranty.
Installation and Mounting
Steps 1-3 are only required if there is no existing exit device at the site.
- Measure 39 13/16" (1011mm) from the finished floor and mark the strike centerline on the door and frame.
- Close the door and mark the latch position on the frame.
- Align the template on the centerline and against the strike.
- Measure the exit device latch position on the door.
- Position the strike on the frame using the marks. Drill a cable access hole and two mounting holes. Loosely mount the strike with Phillips flathead screws.
- Check latchbolt interaction and adjust the strike horizontally until the door latches properly. Tighten mounting screws and mark remaining screw holes.
- Remove the strike and drill the marked holes.
- Wire the device, insert blind nuts, and re-install the strike. Use spacers if necessary to adjust the gap. Secure with hex-socket cap screws.
Wiring and Connection
The device is not polarity sensitive.
- 12 VDC operation: Connect to 12 VDC power supply.
- 24 VDC operation: Connect to 24 VDC power supply.
Fail-safe / Fail-secure Configuration
To change the lock mode:
- Remove the locking screw.
- Loosen the sliding screw.
- Slide the screw to the desired position:
- Fail-Safe: Screws locked AWAY from each other.
- Fail-Secure: Screws locked TOWARDS each other.
- Reinsert and tighten the locking screw.
Manufacturer information
BEA Sensors
Practical help
Common problems
Check latchbolt interaction and adjust the strike horizontally until the door latches correctly.
Always check the placement of all wiring before powering up to ensure moving door parts will not catch any wires.
Adjust the sliding screw position as shown in the configuration diagram; ensure the locking screw is re-tightened.
Before use
- Shut off all power before wiring.
- Verify door frame material (metal or wood).
- Ensure compliance with NFPA70.
- Check for ESD protection before handling circuit boards.
- Verify that all appropriate industry signage and warning labels are in place.
Specs in practice
- Operating voltage
- Supports both 12 VDC and 24 VDC systems.
Model compatibility
- Intended for use with UL-listed, rim type, fire exit hardware (e.g., Von Duprin 99-F).
- Fire rated in fail-secure operation only; using in fail-safe mode negates the fire rating.
- Not for use in fail-secure mode unless permitted by the local Authority Having Jurisdiction (AHJ).
Manual page author
David Miller
Documentation analyst
Organizes user manual content into clear summaries, with attention to model details, product context, and everyday usability.